Cable Sizing for Motors (415 V, 3 Phase, 50 Hz)
Voltage: 415V • Phases: 3-Phase • Frequency: 50Hz
Line Current
—
Phase Current
—
OLR Range (Amp)
—
Fuse (Max., in Amp)
—
Recommended Cable
Al (Sq.mm)
—
Cu (Sq.mm)
—
OLR Range (Amp)
—
Fuse (Max., in Amp)
—
Supply Side
Al (Sq.mm)
—
Cu (Sq.mm)
—
Motor Side
Al (Sq.mm)
—
Cu (Sq.mm)
—
View current carrying capacity by cable specifications
| Size (Sq. mm) |
Core (Number) |
Outer Diameter | Aluminium (Current Rating) | Copper (Current Rating) | |||
|---|---|---|---|---|---|---|---|
| Unarmoured (MM) | Armoured (MM) | In Ground (AMPS) | In Air (AMPS) | In Ground (AMPS) | In Air (AMPS) | ||
* Ratings based on IS 1554 Part 1 standards for PVC insulated cables
| Size (Sq. mm) |
Core (Number) |
Outer Diameter | Aluminium (Current Rating) | Copper (Current Rating) | |||
|---|---|---|---|---|---|---|---|
| Unarmoured (MM) | Armoured (MM) | In Ground (AMPS) | In Air (AMPS) | In Ground (AMPS) | In Air (AMPS) | ||
* Ratings based on IS 7098 Part 1 standards for XLPE insulated cables
View optimal wire size for residential commercial buildings
| Conductor Dia Size (sq.mm) | No. of Wires & Dia of Wires (mm) | Nominal Thickness of Insulation (mm) | Current Carrying Capacity (amp) | Conductor Resistance Ohm/Km (Max, at 20°C) |
|---|---|---|---|---|
| 0.75 | 11/0.3 | 0.6 | 7 | 24.5 |
| 1 | 14/0.3 | 0.7 | 11 | 18.1 |
| 1.5 | 21/0.3 | 0.7 | 13 | 12.1 |
| 2.5 | 36/0.3 | 0.8 | 18 | 7.41 |
| 4 | 56/0.3 | 0.8 | 24 | 4.61 |
| 6 | 84/0.3 | 0.8 | 31 | 3.08 |
| 10 | 140/0.3 | 1.0 | 42 | 1.83 |
| 16 | 224/0.3 | 1.0 | 57 | 1.15 |